Siemens Drive Fault Code 7902 Guide

  • Home
  • /
  • Contex FAQs

Siemens Drive Fault Code 7902 Guide

A: Set p2118 and p2119 to map F7902 to “none”. This is dangerous – motor can stall at low speed with full current, leading to winding burnout. Not recommended.

Introduction In the world of industrial automation, Siemens drives (SINAMICS, MASTERDRIVES, and MICROMASTER families) are renowned for their robustness. However, like any precision electro-mechanical system, they occasionally encounter faults. Fault Code 7902 is one of the less common but critically important alarms that can appear, often leaving maintenance engineers and technicians searching for clear answers. Siemens Drive Fault Code 7902

A: Check p2179 . If set to 10% and your setpoint is 8%, drive thinks you are blocked. Lower p2179 to 3-5%. A: Set p2118 and p2119 to map F7902 to “none”

When a Siemens drive detects that the motor’s actual speed has not followed the setpoint speed within a defined tolerance for a specified time, it triggers this fault. In simple terms: the drive commanded rotation, but the motor shaft did not move (or moved too little). | Parameter | Function | Typical Value | |-----------|----------|----------------| | p2177 | Motor blocked time | 10 seconds | | p2178 | Motor blocked delay time | 0 (immediate) | | p2179 | Speed threshold for blocked detection | 5% of rated speed | Introduction In the world of industrial automation, Siemens

Siemens Drive Fault Code 7902